Point
A Point is a single data item—one concrete quantity to be collected from, or written to, a class of devices. Its definition belongs to a Profile; its runtime value is a PointValue.
A Point answers "which quantities can be read or written on this kind of device." On an air conditioner, "indoor temperature", "set temperature", and "power state" are each a Point; their instantaneous numeric snapshots are PointValues. An analogy: a Profile is the header definition of a table, each Point is one column of it, and a PointValue is the cell a given device fills into that column at a given moment.
Two easy confusions:
- Point ≠ PointValue. A Point is the definition of a "column" (its name, type, writability, unit), and is stable; a PointValue is the value in a "cell", changing as collection proceeds. See PointValue.
- Point ≠ Command. A Point is a "quantity"; a Command is an "action" (reboot, calibrate, switch mode). Whether a Point can be written is decided by its own
rwFlag—it is not, and never registered in thedc3_commandcommand table. Reading/writing a Point goes through thePointCommandpath; custom commands go through theCommandpath.
Key Fields
Point PointBO (table dc3_point):
| Field | Type | Meaning |
|---|---|---|
pointName | String | Point name (for display, e.g. "indoor temperature") |
pointCode | String | Point identifier, unique within a Profile |
pointTypeFlag | PointTypeEnum | Data type, see below |
rwFlag | RwTypeEnum | Read/write capability, see below |
unit | String | Engineering unit, e.g. ℃, kPa |
baseValue | BigDecimal | Offset for linear conversion (default 0) |
multiple | BigDecimal | Multiplier for linear conversion (default 1) |
valueDecimal | Byte | Decimal precision, digits kept for floating-point values (default 6) |
profileId | Long | Owning Profile |
pointExt | PointExt | Extended config (protocol mapping, constraints, collection strategy, etc.) |
enableFlag | EnableFlagEnum | Enable / disable state |
tenantId | Long | Owning Tenant |
Data Type pointTypeFlag
| Enum | code | Meaning |
|---|---|---|
STRING | string | String (default) |
BYTE / SHORT / INT / LONG | byte / short / int / long | Integer |
FLOAT / DOUBLE | float / double | Floating-point |
BOOLEAN | boolean | Boolean |
Read/Write Capability rwFlag
| Enum | code | Meaning |
|---|---|---|
READ_ONLY | r | Read only; can be collected, cannot be written (default) |
WRITE_ONLY | w | Write only; can be written |
READ_WRITE | rw | Readable and writable |
Writability is decided by rwFlag, not the command table
Whether a Point can be written is determined solely by whether its rwFlag includes write capability (WRITE_ONLY or READ_WRITE). This has nothing to do with Command (dc3_command)—Point read/write is not modeled in the command table. The center validates rwFlag before a write command: a write request against a read-only Point is rejected outright.
Raw Value and Engineering Value Conversion
What a Driver reads from a device is often a raw value (a register integer, an ADC count, etc.). A Point converts it to a human-readable engineering value via a linear formula:
engineering value = raw value × multiple + baseValue (then rounded by valueDecimal)Example: a temperature transmitter register reads 2531, configured with multiple = 0.01, baseValue = 0, unit = ℃, valueDecimal = 2; the converted engineering value stored as a PointValue is 25.31 ℃. The defaults multiple = 1, baseValue = 0 mean the raw value equals the engineering value, with no conversion.
Relationship to Other Concepts
- A Point definition hangs under a Profile, alongside Command and Event, together describing "what capabilities this kind of device has."
- A Device belongs to one Profile and thus automatically owns all Points under it; runtime data lands as PointValues keyed by
device_id + point_id.
Example
Configure three Points for an air-conditioner Profile:
| pointCode | pointName | pointTypeFlag | rwFlag | unit | Note |
|---|---|---|---|---|---|
indoor_temp | Indoor temperature | FLOAT | READ_ONLY | ℃ | Collect only, multiple=0.1 for conversion |
set_temp | Set temperature | FLOAT | READ_WRITE | ℃ | Readable, and a new setpoint can be written |
power | Power state | BOOLEAN | READ_WRITE | — | Read current state, write to start/stop |
One air conditioner (device_id=1001) collects an engineering value of 26.5℃ for indoor_temp → it lands as one PointValue. To set it to 22℃, send one write PointCommand against set_temp; because its rwFlag=READ_WRITE, the write request passes validation and is dispatched to the driver.
A Point carries type, read/write, unit, and conversion together
A newly created Point, if not configured explicitly, defaults to type STRING, read/write READ_ONLY, baseValue=0, multiple=1, valueDecimal=6, and an empty unit. When collecting a numeric quantity, remember to change it to the matching numeric type and configure conversion, otherwise it is stored as a raw string.