Industrial Buses & Protocols

Devices on the industrial floor speak dozens of mutually unintelligible "dialects" — PLCs use vendor-proprietary protocols, meters use metering standards, buildings use automation buses. This chapter makes clear what problem each protocol solves, what model it communicates over, how it addresses a single data point, and what to weigh when choosing one. By the end you will be able to read a field device's protocol parameters (register address, byte order, function code) and know how IoT DC3 unifies them into point values.

You are here: the "industrial wired" side of the network layer. For wireless and lightweight IoT protocols see IoT Protocols & Wireless Networks; for where the upstream physical quantities come from see Sensing & Measurement.

What This Layer Is / Why It Exists

To get a temperature from a sensor to the platform, the physical quantity is first turned into an electrical signal by a transmitter, digitized by an acquisition device, and finally transported over the network via some protocol. Industrial protocols are the language contract for that "last mile": they dictate how bytes are ordered, how addresses are encoded, whether it is request-response or subscribe-push, and who is active versus passive.

Why are there so many of them, and why are they such a mess? Because they were born in different eras, industries, and closed vendor ecosystems:

  • Historical baggage. Modbus was created in 1979 for PLC serial communication and is still the most common protocol on the floor; OPC DA is bound to Windows COM/DCOM, a product of the PC era; only later came the cross-platform OPC UA.
  • Vendor walls. Siemens' S7, Mitsubishi's MELSEC (MC protocol), Omron's FINS, Rockwell's EtherNet/IP — every PLC vendor has its own proprietary protocol, mutually incompatible, locking in customers.
  • Industry standards. Power dispatch has IEC 60870-5-104, building automation has BACnet, utility metering has DLMS/COSEM, automotive and embedded have CAN — each industry set a standard for its own needs.

The result: the same "read one value" action addresses differently, frames differently, and represents data types differently across protocols. The value of this layer is understanding the common model behind those differences — once you see that they are all "read/write a value in some address space," the heterogeneity stops being scary.

Key Technologies & Trade-offs

Set syntax details aside and the differences between industrial protocols concentrate in four dimensions: * communication model, addressing, byte order and data types, and polling cadence*. Grasp these four and any unfamiliar protocol becomes approachable.

Three communication models

  • Master/Slave / request-response. A master polls slaves one by one with requests and waits for replies; the slave never speaks unprompted. Modbus, IEC 104 (client issues a general interrogation), S7, MELSEC, and FINS are essentially this model. Simple and deterministic, but the master gets nothing it does not ask for, and real-time-ness is bounded by the poll cycle.
  • Client/Server. More symmetric than master/slave: an OPC UA client can browse the server's address space, read and write on demand, and subscribe — the server pushes when a value changes, sparing needless polling. Powerful, but with heavier handshake and session overhead.
  • Publish/Subscribe. CAN broadcasts ID-tagged frames onto the bus and receivers filter by ID; MQTT (see the wireless side) subscribes by topic. No central polling, naturally suited to multi-receiver, event-driven scenarios.

Addressing: register vs tag vs object

"Which point to read" is a completely different concept across protocols:

  • Numeric address (register / IOA / OBIS). Modbus locates coils/registers by function code + 0-based offset; IEC 104 locates telemetry/telesignal by Information Object Address (IOA); DLMS locates COSEM objects by a 6-segment OBIS code (e.g. 1.0.1.8.0.255 = total active energy). Addresses are numbers, aligned by engineering convention.
  • Symbolic tag (Tag/Item). EtherNet/IP (CIP) addresses by tag name: a variable in the PLC is called Motor_Speed, and the driver reads/writes by name without caring about physical addresses; OPC addresses by NodeId/ItemId. More readable, but the name must match character for character.
  • Object + attribute. BACnet models each quantity as an object (e.g. Analog Input #1) + attribute (Present_Value); DLMS's COSEM objects also have numbered attributes (attribute 2 = current value).

Byte order and data types

Industrial devices are mostly Big-Endian, but when a 32-bit FLOAT spans two 16-bit registers, the register order can still be swapped (four layouts: ABCD / CDAB / BADC / DCBA) — the single most common pitfall on the Modbus floor. The protocol itself often only moves bytes; how to interpret that byte string is decided by configuration: whether it is a 16-bit integer or a 32-bit float, low byte first or high byte first, whether to apply a multiplier and offset. Get the byte order wrong and a float reads as a meaningless large number.

Polling mechanism

Master/slave protocols fetch data by timed polling: too short a cycle overwhelms the device and bus, too long hurts real-time-ness. Subscription protocols (OPC UA, CAN, MQTT) improve on this — they push only on change. In practice points are often grouped by importance: critical quantities polled often, auxiliary ones rarely.

The diagram below groups this chapter's protocols by application domain, each domain mapping to a typical communication model and addressing style:

There is no "best" protocol, only the "most suitable"

Start from what the device itself supports — most field device protocols are fixed by the vendor, and you can only adapt. When you do have a choice, weigh it: pick OPC UA for cross-vendor interoperability; pick a subscription protocol to save bandwidth and go event-driven; pick DLMS for pure meter reading; pick Modbus or CAN for lightweight, low-cost embedded.

Engineering Notes

  • Ports differ per protocol — do not mix them up. Modbus TCP is 502, EtherNet/IP is 44818, IEC 104 is 2404, DLMS over TCP is commonly 4059. Use the wrong port and you will not connect.
  • Addresses are engineering conventions — verify before onboarding. Modbus offset is a 0-based protocol address (" 40001" should be offset=0, not 40001); IEC 104's COT/CA/IOA byte lengths must match the peer exactly, or the whole frame parses misaligned; CIP tag names are case-sensitive and must match character for character.
  • Align data type and byte order with the device. The Point's data type decides how bytes are assembled: a multi-register 32-bit float needs the right register order; a CAN frame payload is sliced by dataOffset/ dataLength/byteOrder. Configure a REAL as a DINT and the float bytes will be parsed as an integer into a meaningless large number.
  • Distinguish read and write services/codes. Modbus reads with 01/02/03/04 and writes with 05/06/15/16; many protocols use different services for read and write, so a writable Point needs a separate write command configured.
  • Fail loudly — never fake success. When a device is unreachable or parsing fails, the right behavior is to record the failure and back off, not to echo a cached value or pretend the write succeeded — the latter leads upper layers to decide on bad data.

How It Lands in IoT DC3

Facing so many heterogeneous protocols, IoT DC3's strategy is: one protocol driver per protocol, confining protocol-layer differences inside the driver, and unifying upward into semantically labeled point values. Whether the underlying layer is a Modbus register, a CIP tag, or an OBIS code, it lands on the platform as the same PointValue of a Point, and the upper layers — storage, query, alarming, AI — need not care about protocol details at all.

DC3 ships 28 drivers in total, and most industrial protocols in this chapter have a corresponding one:

Protocol parameters are driver attributes; the device instance fills the values

Every protocol parameter in this chapter lands in DC3 as an attribute declared by the driver, for which the device instance fills a config value — this mechanism is covered in Attribute and Config. Take Modbus TCP: driver-level attributes host/ port identify the slave, point-level attributes slaveId/functionCode/offset locate the register, and write-command attributes specify the write function code and value template. Switch to EtherNet/IP and the point attributes become tagName/tagType; switch to DLMS and they become logicalName (OBIS) / attributeId. The byte order and register order discussed earlier likewise surface as corresponding point attributes.

In other words, the protocol knowledge in this chapter is not abstract theory — it maps directly to every field you fill in when onboarding a device in DC3. Understand the protocol and you understand the driver's attribute table.

Some drivers are currently protocol skeletons (WIP)

Not every driver has finished its protocol-layer I/O. EtherNet/IP, IEC 104, DLMS, and CAN are currently skeleton implementations: the attribute tables, collection cycles, and addressing semantics are in place and can be filled in, but how far the actual protocol send/receive has progressed varies —

  • IEC 104, DLMS: read()/write() explicitly throw a "not implemented" exception to fail fast (the SDK records the failure and backs off, rather than faking success); the protocol I/O is not yet written.
  • EtherNet/IP: the upper-layer flow (fetch by tag, encode/decode, socket connect) is in place, but the CIP protocol framing (RegisterSession/ForwardOpen/encapsulation frame) is not yet complete.
  • CAN: read()/write() shell out to the Linux can-utils tools (candump/cansend) via ProcessBuilder and can actually send/receive, but byte slicing/type conversion (dataOffset/dataLength, etc.) and native SocketCAN I/O are not yet in place, and the data template on the write path is not actually wired up yet.

Treat them as starting-point templates for the corresponding protocol, not production-ready products. The implementation status on each driver page is authoritative.

Modbus / OPC UA / S7 / BACnet and others are working drivers

Modbus TCP, Modbus RTU, OPC UA, OPC DA, S7, MELSEC, BACnet/IP, and SNMP have implemented protocol-layer read/write; FINS works but its current read path only supports 16-bit types (see its driver page). Before onboarding, defer to the attribute table and notes on each driver page.

Further Reading