PLC S7 Driver

dc3-driver-plcs7 connects Siemens S7 series PLCs to IoT DC3 — it targets the PLC's data blocks (DB), periodically reads register values, and supports writing values back to a DB.

S7 is the proprietary Ethernet protocol used by Siemens PLCs (S7-200/300/400/1200/1500, S7-200 Smart, and so on), running over TCP and used on the industrial floor to read and write the PLC's internal memory areas directly. This driver acts as an S7 client, connecting over TCP to one or more PLCs, then reading data and writing values according to the data block number and offset configured on each Point.

  • Driver name / code: PLC S7 Driver / PlcS7Driver
  • Type: DRIVER_CLIENT (actively connects to the PLC)

Driver configuration (device-level driver-attribute)

When onboarding an S7 PLC device, fill in these attributes on the Device:

AttributecodeTypeDefaultDescription
HosthostSTRING192.168.0.20PLC IP address
PortportINT102S7 TCP port (standard 102)
PLC TypeplcTypeSTRINGS1200PLC model (S200/S200_SMART/S300/S400/S1200/S1500/SINUMERIK_828D)

plcType decides how addresses are resolved

Different S7 PLC models differ in DB addressing and byte order; plcType selects the matching S7 addressing scheme. If it is wrong or an unknown model, the driver falls back to S1200. Common values: use S1200 for S7-1200, S1500 for S7-1500, and S200_SMART for S7-200 Smart.

Point configuration (point-attribute)

Each Point locates a single variable inside a PLC data block. Fill in:

AttributecodeTypeDefaultDescription
DB NumberdbNumINT0Data block number, counted from 0
Byte OffsetbyteOffsetINT0Byte offset within the data block
Bit OffsetbitOffsetINT0Bit offset within the byte (only used for boolean type)

The Point type decides how many bytes are read

The driver derives the read width from the Point's data type (the pointTypeFlag of the Point) starting at byteOffset: BOOLEAN takes the single bit at byteOffset.bitOffset, SHORT reads 2 bytes, INT/FLOAT read 4 bytes, LONG/DOUBLE read 8 bytes, and STRING reads a string. So bitOffset only matters on boolean Points and is ignored for the other types.

Write command configuration

This driver supports writing values to the PLC, but has no separate write-command attributes (application.yml has no command-attribute). Writing a Point reuses that Point's own point-attribute (dbNum / byteOffset / bitOffset) to locate the address, and the write width is determined by the value type carried by the command. In other words: once a writable Point has the three items above configured, it can be both read and written — no extra configuration is needed.

Collection and health

  • Collection cycle: default cron 0/30 * * * * ? (one read round every 30 seconds).
  • Health/online: device health check defaults to cron 0/15 * * * * ?, with a lease timeout of 45 seconds — see Device for the online-status mechanism.

Minimal onboarding example

Onboard an S7-1200 PLC at IP 192.168.0.20:102 and read a 32-bit float at offset 0 in DB1:

  1. Create a Device using PLC S7 Driver, and set the driver attributes host=192.168.0.20, port=102, plcType=S1200.
  2. Add a temperature Point (pointTypeFlag=FLOAT) to the Profile bound to the device, and set the point attributes dbNum=1, byteOffset=0, bitOffset=0.
  3. Start the driver, and within 30 seconds you will see the collected value in PointValue.

Common pitfalls

The PLC side must allow PUT/GET access

S7-1200/1500 block external PUT/GET communication by default. In TIA Portal you must check "Permit access with PUT/GET communication from remote partner", otherwise the connection can be established but reads/writes will fail. The DB being accessed must also have "Optimized block access" turned off, so the driver can locate variables by byte offset.

bitOffset only applies to boolean Points

Non-boolean types (SHORT/INT/FLOAT, etc.) look only at byteOffset; bitOffset is ignored. Setting bitOffset on a float Point causes no error but has no effect — do not use it to "skip" bytes; to move across bytes, change byteOffset.

One driver instance can serve multiple PLCs

A single PLC S7 driver process can serve multiple devices; each PLC is distinguished by the host (and plcType) on its own Device, and connections are reused per deviceId with automatic reconnect.