SNMP Driver

dc3-driver-snmp connects SNMP-capable network and data-center devices to IoT DC3: it targets an OID on the device's MIB tree, periodically sends SNMP GET to read values, and supports sending SNMP SET to an OID to write values. By the end you will be able to onboard a router, switch, or UPS and collect its port status, traffic, temperature/humidity, and other metrics as PointValues.

Protocol background

SNMP (Simple Network Management Protocol) is the most common management protocol for network and data-center equipment. It runs over UDP on default port 161. It belongs to the network layer of the IoT four-layer architecture — like Modbus and OPC on the industrial floor, it solves the problem of "reading/writing a value in some address space," except its devices are not PLCs and meters but IP network elements: routers, switches, UPSes, rack PDUs, printers, server NICs.

Each managed device holds a MIB (Management Information Base) tree, and every readable/writable data point on that tree has a unique object identifier OID (Object Identifier, e.g. 1.3.6.1.2.1.1.1.0). A manager uses the OID to locate " which value to read":

  • Scalar objects end with the instance identifier .0, e.g. the system description sysDescr is 1.3.6.1.2.1.1.1.0;
  • Table entries (such as per-port traffic or status) end with a row index, e.g. ...10.1 and ...10.2 for ports 1 and 2.

SNMP has three versions: v1 / v2c / v3. v1 and v2c use a cleartext community string as the passphrase — simple to configure and the most common in the field; v3 introduces USM (User-based Security Model) for authentication and encryption. Built on the SNMP4J library, this driver acts as an SNMP manager and actively connects to devices: a read Point sends a GET to its OID, a write Point sends a SET to the OID, and one long-lived SNMP session is reused per device.

The typical use case is data-center and network monitoring — bandwidth, port up/down, CPU/memory utilization, room temperature/humidity, UPS battery, etc. Any SNMP-capable device can be managed once its OIDs are configured.

IoT DC3Network devices (SNMP Agent)GET oid (UDP 161)SET oid (UDP 161)response: VariableBindingdc3-driver-snmpSNMP Manager (SNMP4J)Switch / RouterUPS / PDUServer NIC

Attribute configuration

SNMP connection parameters and collection targets are filled in at two levels: connecting to a device uses driver attributes (device-level), and locating each data point uses point attributes (point-level). The attribute names, types, and defaults all come from the driver application.yml driver-attribute / point-attribute / command-attribute definitions.

Driver attributes (device-level driver-attribute)

When onboarding an SNMP device, fill in these Attributes on the Device. host / port decide which device and UDP port to connect to, version + community are the v1/v2c identity passphrase, and timeout / retries control request fault tolerance.

AttributecodeTypeDefaultDescription
HosthostSTRING127.0.0.1SNMP device IP
PortportINT161SNMP port (standard 161)
VersionversionSTRINGv2cSNMP version (v1 / v2c)
CommunitycommunitySTRINGpublicCommunity string (read-only / read-write passphrase)
USM UsernameusmUsernameSTRING(empty)SNMPv3 USM username (not used in v1/v2c)
USM Auth ProtocolusmAuthProtocolSTRINGMD5SNMPv3 auth protocol (MD5/SHA)
USM Auth PasswordusmAuthPasswordSTRING(empty)SNMPv3 auth password
TimeouttimeoutINT5000Request timeout in milliseconds
RetriesretriesINT1Number of request retries

The three USM fields are reserved for SNMPv3 and have no effect today

usmUsername / usmAuthProtocol / usmAuthPassword are the SNMPv3 USM security fields. They are declared in application.yml, but the driver's buildTarget() builds only a CommunityTarget and sets version1 or version2c based on version. The current implementation supports only v1 and v2c, so these three are never read even if filled in; set version to v1 or v2c.

validate() marks host / port / version / community as required — missing any one fails device validation.

Point attributes (point-attribute)

On each collected Point, fill in oid to specify which data point to read; snmpType labels that value's SNMP data type.

AttributecodeTypeDefaultDescription
OIDoidSTRING(empty)SNMP object identifier (e.g. 1.3.6.1.2.1.1.1.0)
SNMP TypesnmpTypeSTRINGOCTET_STRINGSNMP data type (INTEGER/GAUGE32/COUNTER32/OCTET_STRING/TIMETICKS/IPADDRESS/OID)

The OID selects which data point is collected; snmpType is mainly for writes

On read, the driver sends a GET to the configured oid and reports the returned VariableBinding value as-is via variable.toString() as the PointValuesnmpType is not used in reads. Its real role is on write: createVariable() uses it to convert the string into the correct SNMP variable type. validatePoint() marks oid as required, so a read Point missing oid fails validation.

Writes reuse the point attributes — no separate write command needed

Writes and reads share the same oid / snmpType on the Point: write() (SET) reads oid and snmpType from pointConfig (point-attribute), sends a SET to that OID, and builds the value per snmpType. A writable Point only needs oid and snmpType configured on the point — no need to repeat them on a write command.

snmpType values supported by createVariable(): INTEGER/INTEGER32, GAUGE32/COUNTER32/UNSIGNED_INTEGER32, COUNTER64, TIMETICKS, OID, IPADDRESS, NULL; anything else is treated as OCTET_STRING.

command-attribute is not read by the write path today

application.yml declares a command-attribute (oid / snmpType), but write()'s signature only takes driverConfig and pointConfig — command attributes are not passed in, and this driver does not override execute(). So that command-attribute is a placeholder declaration today and is never read on write. Configure a writable Point's oid / snmpType on the Point itself, not on a write command — otherwise the write falls back to the point defaults ( oid empty, snmpType=OCTET_STRING).

Collection and health

  • Collection cycle: default cron 0/30 * * * * ? (one read every 30 seconds, from schedule.read.cron).
  • Health / online: device health check default cron 0/15 * * * * ?, lease timeout 45 seconds. health() decides online by "whether the device has an established SNMP session" — if clientMap holds the device it is treated as online; otherwise it tries to build a session, and online once built. See Device for the online-state mechanism.

An established SNMP session does not mean the device is reachable

getConnector() builds a local UDP transport (DefaultUdpTransportMapping); once listen() succeeds it is cached as " online" without probing the device. So after a device goes offline, the health check may briefly still report online — a real failure only surfaces on the next read() timeout, at which point the driver does clientMap.remove(deviceId) to destroy the session, and the next health check flips to offline.

Troubleshooting

Scalar OIDs usually end with .0 — don't drop it

A scalar (single-value) object's OID ends with the instance identifier .0, e.g. sysDescr is 1.3.6.1.2.1.1.1.0, not 1.3.6.1.2.1.1.1. Table entries (such as per-port traffic) end with a row index instead (e.g. ...10.1, ...10.2). When the OID is wrong, the device returns noSuchObject/noSuchInstance, and variable.toString() reports it as a plain string PointValue — it looks like "collected" but is invalid data, which is easy to be misled by during diagnosis.

A wrong community times out silently

SNMP uses the community string as its passphrase. If the community does not match, or the device does not grant that community access, the device usually sends no reply; the response.getResponse() from snmp.send() is null and the driver throws ReadPointException("SNMP response is null..."). This shows up as a request timeout rather than an explicit "auth failed." Before onboarding, confirm the host, port, community, and oid combination returns a value on the command line with snmpget -v2c -c public <host> 1.3.6.1.2.1.1.1.0.

Firewall blocks UDP 161 / device has SNMP disabled

SNMP runs over UDP, not TCP; many firewalls pass TCP by default but block UDP, and switches/servers often have the SNMP agent disabled by default. The symptom is again a timeout. First confirm the target device has the SNMP service enabled and that inbound UDP 161 traffic from the manager to the device is allowed.

Before onboarding, verify the link on the command line with net-snmp tools — the driver uses the same SNMP4J semantics, so if the command line returns nothing, don't create the device in DC3 yet:

bash
# Minimal connectivity check
snmpget -v2c -c public 192.168.1.20:161 1.3.6.1.2.1.1.1.0
# If no value comes back, rule out each: host pingable? UDP 161 open? community correct? SNMP enabled?
snmpwalk -v2c -c public 192.168.1.20:161 1.3.6.1.2.1.1   # walk the system subtree to see if the device answers

version only accepts v1 / v2c — v3 is treated as v2c

The driver's buildTarget() only recognizes v1 (case-insensitive); any other value — including v3 — falls through to the version2c branch. If the device only allows SNMPv3, this driver cannot connect, and there is no explicit " version unsupported" error — it just shows up as a community-validation timeout. Make sure the device allows v1/v2c access.

A write returning true does not mean the device accepted it

write() returns true as soon as it gets a non-null response; it does not check the response PDU's errorStatus. Some devices return a response with an error code (rather than no reply) for a read-only OID or an unauthorized write, and the driver still treats it as success. After writing a critical parameter, read the OID back to confirm it took effect.

How it lands in IoT DC3

  • dc3.driver.code: SnmpDriver (driver name SNMP Driver, type DRIVER_CLIENT, actively connects to devices). This is a stable routing identifier and must not be changed casually.
  • Read / write / subscribe capability: read ✓, write ✓, subscribe —, consistent with the driver capability matrix. The driver polls actively as an SNMP manager and does not listen for device pushes, so there is no subscribe direction.

Implementation status: available

In SnmpDriverCustomServiceImpl, read() (GET), write() (SET), getConnector() (session management), health(), and event() (destroying a session on device update/delete) are all implemented; the SNMP4J v1/v2c send/receive path is complete and usable. Known boundaries: SNMPv3/USM is not wired up (see the three USM fields above), write() does not check the response errorStatus, and the health check is a local session-liveness check rather than an end-to-end probe. These are deliberate trade-offs in the current implementation and do not affect normal v1/v2c collection and writes.

Minimal onboarding example — onboard a switch at IP 192.168.1.20:161 with community public, collecting its system description (sysDescr, OID 1.3.6.1.2.1.1.1.0):

  1. Choose SNMP Driver to create a Device, filling the driver attributes host=192.168.1.20, port=161, version=v2c, community=public.
  2. Add a description Point (pointTypeFlag=STRING, READ_ONLY) to the Profile bound to the device, with the point attribute oid=1.3.6.1.2.1.1.1.0.
  3. Start the driver; within 30 seconds the device's system description string appears in the PointValue.

See Device onboarding for the full flow.