BACnet/IP Driver

dc3-driver-bacnet-ip connects BACnet/IP devices to IoT DC3. It joins the network as a local BACnet device, discovers remote devices via broadcast, periodically reads object property values, and supports writing values to writable object properties. After reading this you can configure local networking parameters on a Device, locate a remote data point on a Point by "object type + instance number + property", and diagnose the common "can't discover the device / reading the wrong object / can't write" problems.

You are here: a concrete driver on the building-automation side of the network layer. For BACnet's object-property addressing model and its place in the four-layer architecture, see Industrial Buses & Protocols.

Protocol Background

BACnet (Building Automation and Control network) is an international standard protocol for building automation (ASHRAE 135 / ISO 16484-5), in wide use since 1995 for HVAC units, fresh-air systems, lighting, elevators, chiller/boiler plants, thermostats, and other mechanical/electrical equipment. Its goal is interoperability across building equipment from different vendors, so it abstracts "device capability" into a unified object model rather than binding to specific hardware.

BACnet/IP is the variant of BACnet that runs over Ethernet: it wraps BACnet application-layer messages in UDP, listening on port 47808 by default (i.e. 0xBAC0). Compared with the earlier MS/TP serial or ISO 8802-3 Ethernet forms, BACnet/IP reuses the existing IP network directly and discovers devices within a subnet via UDP broadcast — which also imposes one hard constraint: broadcast does not cross layer-3 routing by default (see Troubleshooting below).

In the four-layer IoT architecture, BACnet/IP belongs to the building-automation side of the network layer: it defines how mechanical/electrical equipment is addressed and read/written on the network, carrying the temperatures, states, and metering values gathered by the sensing layer up to the platform. Its communication model is master/slave, request-response — this driver acts as the initiator (client), actively discovering and accessing remote devices and polling on a cron cycle; remote devices do not report on their own.

BACnet addressing is a three-level structure, and understanding it is understanding how to configure a Point:

broadcast discover remoteDeviceIdobjectType + instancepropertyId read/writedc3-driver-bacnet-ipLocalDeviceRemote Devicedevice instanceObjectobjectType + objectInstancePropertypropertyId · e.g. PRESENT_VALUE

A physical device is identified by a unique device instance number; it contains a number of objects (such as ANALOG_INPUT, BINARY_OUTPUT), each located by "object type + object instance number"; and each object exposes several properties, the most common being PRESENT_VALUE (the current value). Reading or writing a point is essentially locating the path "remote device → object → property".

  • Driver name / code: BACnet IP Driver / BacnetIpDriver
  • Type: DRIVER_CLIENT (the driver actively discovers and accesses remote devices)

Attribute Configuration

Onboarding a BACnet/IP device requires filling in attributes at three levels: device-level local networking parameters (driver-attribute), the addressing parameters of each collected point (point-attribute), and the write-command parameters of each writable point (command-attribute). The attributes, types, and defaults below all come from the driver's application.yml (the dc3-driver-bacnet-ip module).

Driver Attributes (device-level driver-attribute)

Driver attributes answer "what identity the driver uses, which NIC it binds, and how it broadcasts" — note that these configure how the local driver joins the network, not the remote device address; the remote device is located by remoteDeviceId on the Points below. Fill in one set per device on the Device:

AttributecodeTypeDefaultDescription
Local Device IDlocalDeviceIdINT1001Local BACnet device instance number
Bind AddressbindAddressSTRING0.0.0.0Local bind address
PortportINT47808BACnet UDP port (default 47808 = 0xBAC0)
Broadcast AddressbroadcastAddressSTRING255.255.255.255Broadcast address for device discovery
TimeouttimeoutINT6000Request timeout in milliseconds

localDeviceId is the instance number the driver occupies when it joins the network as a LocalDevice; it must not collide with the instance number of any existing BACnet device on the network. bindAddress defaults to 0.0.0.0, letting the system pick the NIC; specify a concrete NIC IP only when the host has multiple NICs or the broadcast cannot reach the target subnet. broadcastAddress is the address used to broadcast when discovering remote devices; the default 255.255.255.255 is a limited broadcast, and for cross-subnet onboarding you should change it to the directed broadcast address of the target subnet. The driver caches connections by device ID (one LocalDevice per device), and the underlying transport timeout takes timeout. Config validation (validate) requires localDeviceId, bindAddress, and port to be non-empty.

Point Attributes (point-attribute)

Point attributes answer "which property of which object on which remote device to read". Fill in one set per collected Point:

AttributecodeTypeDefaultDescription
Remote Device IDremoteDeviceIdINT0Remote BACnet device instance number
Object TypeobjectTypeSTRINGANALOG_INPUTBACnet object type (see enum below)
Object InstanceobjectInstanceINT0Object instance number
Property IDpropertyIdSTRINGPRESENT_VALUEProperty identifier

remoteDeviceId is the instance number of the remote device to read; the driver first discovers the device by broadcast using it, then locates the object by objectType + objectInstance and fetches the property by propertyId. Both objectType and propertyId are matched by their exact uppercase enum name, drawn from a fixed mapping table in the code (see the pitfall below and "How it lands in IoT DC3"). Config validation (validatePoint) requires all four to be non-empty.

Write Command Attributes (command-attribute)

Writable points also need one set on the write command, with the same structure as the point attributes but defaulting to a writable output object:

AttributecodeTypeDefaultDescription
Remote Device IDremoteDeviceIdINT0Remote BACnet device instance number
Object TypeobjectTypeSTRINGANALOG_OUTPUTBACnet object type to write
Object InstanceobjectInstanceINT0Object instance number
Property IDpropertyIdSTRINGPRESENT_VALUEProperty identifier

The written value is auto-encoded by the target object type (see the "Write value encoding" tip below).

Object Type / Property ID must use the exact uppercase enum name, or it silently falls back

objectType and propertyId are matched by their exact uppercase names. A wrong or misspelled value **raises no error ** — the driver's resolveObjectType() / resolvePropertyIdentifier() silently falls back to ANALOG_INPUT / PRESENT_VALUE, so you may read the value of a different object without noticing.

  • objectType is supported in code for 10 types: ANALOG_INPUT, ANALOG_OUTPUT, ANALOG_VALUE, BINARY_INPUT, BINARY_OUTPUT, BINARY_VALUE, MULTI_STATE_INPUT, MULTI_STATE_OUTPUT, MULTI_STATE_VALUE, DEVICE (the yml remark lists only the first 9; DEVICE also works — defer to the code).
  • propertyId supports 7: PRESENT_VALUE, DESCRIPTION, STATUS_FLAGS, EVENT_STATE, RELIABILITY, UNITS, OUT_OF_SERVICE.

Troubleshooting

BACnet/IP onboarding failures cluster into three kinds: broadcast discovery, object addressing, and write-value encoding. Work through them in order:

  1. Device stays offline / connection creation fails. When the driver joins the network with localDeviceId, if that instance number collides with an existing device, or binding the port/NIC fails, LocalDevice.initialize() throws ConnectorException and the device stays offline. First confirm localDeviceId is unique on the network, port 47808 is not occupied by another BACnet program on the same host, and bindAddress points to a real, usable NIC.

  2. Connected but reads keep timing out (stuck until timeout). The driver relies on getRemoteDeviceBlocking(remoteDeviceId) to block while broadcasting for the remote device — if remoteDeviceId is not found on the network it blocks until timeout and then throws ReadPointException. First check whether remoteDeviceId is exactly the target device's instance number; then confirm the driver and the target device are in the same broadcast domain (see the pitfall below).

  3. Read value is wrong / looks like a different point. Most likely objectType or propertyId is misspelled and triggered the silent fallback (back to ANALOG_INPUT / PRESENT_VALUE). Check the uppercase enum name character by character and confirm it is in the supported list above.

  4. Write command fails. First confirm the target object type is writable (*_INPUT objects are usually physically read-only and cannot be written), then confirm the input value matches the encoding rules (see "Write value encoding" below). A failed write throws WritePointException.

  5. Can't reach devices across subnets / on a multi-NIC host. BACnet/IP uses UDP broadcast, which does not cross layer-3 routing by default. See the pitfall container below.

  6. Online status flapping. The health check defaults to once every 15 seconds (cron 0/15 * * * * ?) with a 45-second lease timeout; the driver judges online status by LocalDevice.isInitialized(). Frequent online/offline flapping usually means packet loss or unstable local-device initialization — see Device for the online-status mechanism.

Write value encoding is determined by the object type

The driver's createEncodable() decides how to encode the written value by the object type prefix: ANALOG_* is written as a float (Real); BINARY_* treats true / 1 / active (case-insensitive) as "active" and everything else as "inactive"; MULTI_STATE_* and DEVICE are written as an integer (UnsignedInteger); a non-numeric value that lands on the analog branch degrades to a string (CharacterString). So to toggle a BINARY_OUTPUT, send 1 or true rather than ON.

The remote device must be discoverable via broadcast

The driver can only read and write after discovering the remote device on the network via broadcast. BACnet/IP uses UDP broadcast, which normally cannot cross layer-3 routing — make sure the driver and the target device are in the same broadcast domain. Across subnets, deploy a BBMD (BACnet/IP Broadcast Management Device) on the network and change broadcastAddress to the directed broadcast address of the target subnet. An unfound remoteDeviceId blocks until timeout (see Troubleshooting item 2 above).

How it lands in IoT DC3

  • dc3.driver.code: BacnetIpDriver (type DRIVER_CLIENT, actively discovers and accesses remote devices). This is a stable routing identifier — do not change it casually.
  • Read: ✓ implemented. Discovers the device by broadcast using remoteDeviceId, reads the object property by objectType + objectInstance + propertyId, and returns the result as a string.
  • Write: ✓ implemented. Auto-encodes the written value by object type (see the "Write value encoding" tip above).
  • Subscribe/report: — not supported. BACnet is a master/slave polling model; this driver only actively reads/writes and never passively receives pushes (COV subscription is not implemented). This matches the "✓ / ✓ / —" for BACnet/IP in the driver capability matrix.
  • Collection cycle: default cron 0/30 * * * * ? (one read round every 30 seconds), configured under schedule.read in the driver's application.yml.
  • Health/online: device health check defaults to cron 0/15 * * * * ?, with a lease timeout of 45 seconds, judged by LocalDevice.isInitialized().

Implementation status: available

This driver is a complete implementation (not a skeleton), built on BACnet4J. read() / write() issue real BACnet read/write requests, health() judges online status by the local device's initialization state, validate() / validatePoint() perform required-field checks, and it caches the LocalDevice connection by device ID. Note two behaviors that differ from intuition: (1) a misspelled objectType / propertyId silently falls back rather than erroring; (2) an unfound remoteDeviceId blocks until timeout — both covered above.

schedule.custom is enabled but is a no-op

The driver's application.yml declares schedule.custom (cron 0/5 * * * * ?, enable: true), but the schedule() method is an empty implementation (no custom periodic logic). That is, this custom schedule currently produces no collection behavior; actual collection is driven only by schedule.read — defer to the code.

Minimal Onboarding Example

Onboard the temperature object of a BACnet/IP device whose device instance number is 9001 on the network:

  1. Create a Device using BACnet IP Driver. The driver attributes can all keep their defaults (localDeviceId=1001, bindAddress=0.0.0.0, port=47808, broadcastAddress=255.255.255.255, timeout=6000); adjust bindAddress / broadcastAddress only when the host has multiple NICs or the broadcast cannot reach the target subnet.
  2. Add a temperature Point (READ_ONLY) to the Profile bound to the device, with point attributes remoteDeviceId=9001, objectType=ANALOG_INPUT, objectInstance=1, propertyId=PRESENT_VALUE.
  3. Start the driver, and within 30 seconds the object's PRESENT_VALUE appears in the PointValue.
  4. If the Point must be writable, configure a write Command for it, set objectType explicitly to a writable output object (e.g. ANALOG_OUTPUT), and send the value per the object-type rules (a number for analog, 1/true for binary).

One driver instance can serve multiple devices

A single BACnet/IP driver process can serve multiple devices, each holding its own cached LocalDevice by device ID, with the target remote device distinguished by remoteDeviceId on the Point.