Modbus TCP Driver

dc3-driver-modbus-tcp connects Modbus TCP slave devices to IoT DC3. It acts as the Modbus master (client), periodically reads coils/registers over Ethernet, and supports writing values to coils and holding registers. By the end you can set host/port on a Device, set function codes and addresses on a Point, and troubleshoot the common "no value read / write won't go through" problems.

You are here: a concrete driver on the "industrial wired" side of the network layer. For the protocol-level addressing model, byte order, and function-code concepts, see Industrial Buses & Protocols.

Protocol background

Modbus dates back to 1979, originally a master/slave protocol Modicon designed for PLC serial communication, and it is still one of the most common protocols on the industrial floor — heavily used by PLCs, power meters, VFDs, and sensor gateways. It is simple, open, and publicly documented, which is why every vendor implements it.

Modbus TCP is the Ethernet encapsulation of Modbus: it wraps the Modbus application-layer message (PDU) that originally ran over an RS-485 serial line into TCP/IP, listening on port 502 by default. Compared with the serial Modbus RTU, the TCP variant drops the CRC check (TCP guarantees integrity) and prepends a 7-byte MBAP header for transaction identification. A single Ethernet segment can host many slaves, and a Modbus TCP gateway can bridge to multiple serial slaves behind it.

In the four-layer IoT architecture, Modbus TCP belongs to the network layer, industrial-wired side: it defines how a field device is addressed and read/written over the network, moving the physical quantities sampled at the perception layer up to the platform. Its communication model is the classic master/slave, request/response — a slave stays silent until polled, so the IoT DC3 driver, acting as master, polls on a cron cycle.

Modbus data is organized into four register spaces, distinguished on read by the function code:

FC01 readFC02 readFC03 readFC04 readFC05/06 writedc3-driver-modbus-tcpModbus masterCoilsR/W · bitDiscrete Inputsread-only · bitHolding RegistersR/W · 16-bitInput Registersread-only · 16-bit

Coils and discrete inputs are single bits (digital), while holding and input registers are 16-bit words (analog). A 32-bit FLOAT or LONG occupies two consecutive registers, and a 64-bit DOUBLE occupies four — the driver assembles multi-register quantities automatically based on the Point's data type.

Attribute configuration

Onboarding a Modbus TCP device means filling attributes at three levels: device-level connection parameters (driver-attribute), per-collected-point addressing parameters (point-attribute), and per-writable-point write-command parameters (command-attribute). The attributes, types, and defaults below all come from the driver's application.yml (the dc3-driver-modbus-tcp module).

Driver attributes (device-level driver-attribute)

Driver attributes answer "which slave do I connect to". Fill one set on each Modbus TCP Device:

AttributecodeTypeDefaultDescription
HosthostSTRINGlocalhostModbus slave IP or hostname
PortportINT502Modbus TCP port (standard 502)

host + port uniquely identify a TCP connection. The driver caches one connection per device ID (one ModbusMaster per device), and the socket timeout is fixed at 5 seconds. During config validation, port must fall within 1–65535.

Point attributes (point-attribute)

Point attributes answer "which data point on this slave do I read". Fill one set on each collected Point:

AttributecodeTypeDefaultDescription
Slave IDslaveIdINT1Modbus slave unit ID
Function CodefunctionCodeINT1Read function code, only [1, 2, 3, 4] supported
OffsetoffsetINT0Register/coil address offset (0-based)

slaveId distinguishes multiple slaves behind the same IP (gateway). functionCode decides which register space to read, and validation forces it into 1–4:

The function code decides which register space gets read

Reading uses 01 (coils) / 02 (discrete inputs) / 03 (holding registers) / 04 (input registers). The Point's data type (the pointTypeFlag of the Point) must match the data width returned by the function code — the driver maps types to Modbus data widths: LONG→4-byte int, FLOAT→4-byte float, DOUBLE→8-byte float, others (e.g. INT)→2-byte int. Multi-register quantities are assembled across registers automatically per Point type.

Write command attributes (command-attribute)

A writable Point also needs one set on the write command, answering "which address to write and what value":

AttributecodeTypeDefaultDescription
Slave IDslaveIdINT1Slave unit ID
Function CodefunctionCodeINT6Write function code (yml lists [5, 6, 15, 16], but see implementation status below)
OffsetoffsetINT0Address offset (0-based)
Value TemplatevalueTemplateSTRING${value}Value template, rendered with command params

valueTemplate defaults to ${value}, meaning the value passed in the command is written as-is; change the template when a transform is needed (such as multiply-by-factor or add-offset). How the value is encoded into registers is determined by the Point's pointTypeFlag.

Write function code: yml lists 4, the implementation honors only 2

application.yml annotates the write function codes as [5, 6, 15, 16] with default 6, but the current ModbusTcpDriverCustomServiceImpl.writeValue() handles only functionCode=1 (write single coil) and * *functionCode=3 (write single holding register)**. Any other code (including the default 6) falls to the default branch and returns false (write failed). So set the command's functionCode explicitly to 3 to write a register or 1 to write a coil — do not keep the default 6. The semantics of FC05/06/15/16 are not yet implemented in code — the code is the source of truth.

Troubleshooting

Most Modbus TCP onboarding failures cluster into three classes: connection, addressing, and byte order. Work through them in this order:

  1. Port/connection unreachable (device stays offline). First confirm the slave IP and port 502 are reachable: telnet <host> 502 or nc -vz <host> 502. The driver's socket timeout is 5 seconds; a failed connect throws ConnectorException. Note: after 3 consecutive connection failures the driver enters a 60-second backoff, during which the health check reports offline immediately without retrying — once the network is fixed it recovers automatically within at most one backoff window.

  2. Connects but reads nothing / errors. Check that the Point's slaveId is correct (mismatches are common with multiple slaves behind a gateway) and that functionCode matches the actual register type at that address (using 03 for holding registers against a read-only discrete input throws an exception). A failed read throws ReadPointException, invalidates that device's connection, and reconnects on the next cycle.

  3. offset filled in as an address like 40001. This is the most frequent mistake — see the pitfall container below. offset is a 0-based protocol offset, not the PLC-conventional 4xxxx numbering.

  4. Wrong value / bytes swapped (byte order). 32/64-bit values span multiple registers, and devices differ in their word-order/byte-order conventions. The driver reads with the default word order of the underlying modbus4j — if a float comes out clearly garbled (e.g. 25.0 read as an astronomical number), the device-side word order usually differs from the default. The driver attributes do not currently expose a word-order switch, so for such devices adjust the register mapping on the device side, or read as integers and convert yourself.

  5. Write command returns failure. First confirm functionCode is 1 or 3 per the "write function code" warning above; if it still fails, check the target is a writable space (discrete inputs 02 and input registers 04 are physically read-only and cannot be written). A failed write throws WritePointException and invalidates the connection.

  6. Flapping online status. The health check runs every 15 seconds by default, with a 45-second lease timeout. If a device flaps between online/offline, it is usually packet loss or a slave responding slower than the 5-second timeout — see Device for the online-status mechanism.

offset is a 0-based protocol address, not 40001

offset is the protocol-layer 0-based offset. To read "holding register 40001" in the conventional Modbus notation, set functionCode=3 and offset=0 (the 2nd holding register is offset=1, and so on). Putting 40001 directly into offset reads the wrong address or errors out of range.

How it lands in IoT DC3

  • dc3.driver.code: ModbusTcpDriver (type DRIVER_CLIENT, actively connects to the slave). This is a stable routing identifier — do not change it casually.
  • Read: ✓ implemented. Supports function codes 1/2/3/4 (coils/discrete inputs/holding registers/input registers), assembling multi-register quantities by Point type.
  • Write: ✓ implemented, but only functionCode=1 (write coil) and functionCode=3 (write holding register); other codes return failure (see the write function-code warning above).
  • Subscribe/report: — not supported. Modbus is a master/slave polling model; the driver only actively reads/writes and never passively receives pushes. This matches the "✓ / ✓ / —" for Modbus TCP in the driver capability matrix.
  • Collection cycle: default cron 0/30 * * * * ? (one read round every 30 seconds), configured under schedule.read in the driver's application.yml; the custom schedule is disabled by default.
  • Health/online: device health check defaults to cron 0/15 * * * * ?, with a lease timeout of 45 seconds.

Implementation status: available

This driver is a complete implementation (not a skeleton), built on modbus4j. The read path covers all four register spaces, the write path covers coils and holding registers, and it includes connection caching and failure backoff. The only caveat is that the yml annotation for write function codes ([5,6,15,16]) is broader than the code (only 1/3) — configure explicitly per the warning above and it works.

Minimal onboarding example

Onboard a Modbus slave at IP 192.168.1.10:502:

  1. Create a Device using Modbus TCP Driver, and set the driver attributes host=192.168.1.10 and port=502.
  2. Add a temperature Point (pointTypeFlag=FLOAT, READ_ONLY) to the Profile bound to the device, and set the point attributes slaveId=1, functionCode=3, offset=0.
  3. Start the driver, and within 30 seconds you will see the collected value in PointValue.
  4. If the Point must be writable, configure a write Command for it and set functionCode explicitly to 3 (write holding register).

One driver instance can serve multiple slaves

A single Modbus TCP driver process can serve multiple devices. When several slaves hang off the same gateway under different unit IDs, host is the same and they are distinguished by the Point's slaveId; devices at different IPs each hold their own cached connection.

Further reading