OPC UA Driver

dc3-driver-opc-ua connects OPC UA servers to IoT DC3: acting as an OPC UA client, it connects to one or more servers, periodically reads node values according to the namespace and identifier configured on each Point, and supports writing values to nodes. After reading this page you can onboard an OPC UA device, configure its points, and troubleshoot the common reasons a connection fails.

Protocol background

OPC UA (OPC Unified Architecture) is the cross-platform data-interoperability standard for industrial automation. PLCs, SCADA, MES, and edge gateways commonly embed an OPC UA server that exposes field data as a "node tree." It supersedes classic OPC (the Windows DCOM-based OPC DA), replacing it with the platform-independent opc.tcp:// binary protocol (HTTPS is also supported) and building security (certificates, signing, encryption) and information modeling into the spec.

In the four-layer IoT architecture, OPC UA belongs to the network layer (fieldbus): it is the protocol boundary between shop-floor devices and upper systems, facing PLCs/controllers downward and handing data to the data platform upward. Unlike Modbus, which addresses by register, or Ethernet/IP, which uses CIP tags, OPC UA addresses with an object model — every data point is a node, uniquely identified by a NodeId. A NodeId has two parts:

  • namespace index: an integer that separates identifier spaces from different sources to avoid collisions.
  • identifier: the node's name within that namespace — a string, numeric, or GUID. This driver uses string identifiers.

For example, namespace=2 with identifier Demo.Static.Float uniquely locates the node named Demo.Static.Float under namespace 2. The driver is built on Eclipse Milo and acts as the OPC UA client, actively connecting to the server — a classic "master polling" model: it does not listen for device-pushed updates but reads nodes one by one on each collection cycle.

  • Driver name / code: OPC UA Driver / OpcUaDriver
  • Type: DRIVER_CLIENT (actively connects to the server)
OPC UA Server (PLC / SCADA / gateway)Node Treenode ns=2;s=Demo.Static.Floatnode ns=2;s=Demo.Static.Boolopc.tcp://host:port read/writedc3-driver-opc-uaOPC UA client (Eclipse Milo)PointValue reportIoT DC3 Data Center

Attribute configuration

OPC UA onboarding parameters come in two layers: driver attributes on the Device say "which server to connect to," and point attributes on each Point say "which node to read/write." Both layers originate from the driver's application.yml; fill them in when creating a device/point, or leave them blank to use the defaults below.

Driver attributes (device-level driver-attribute)

These three attributes combine into the endpoint address opc.tcp://<host>:<port><path>, telling the driver which endpoint of which OPC UA server to connect to.

AttributecodeTypeDefaultDescription
HosthostSTRINGlocalhostServer hostname or IP
PortportINT18600Server opc.tcp listening port
PathpathSTRING/Endpoint path

For example, host=192.168.1.20, port=4840, path=/milo combine into opc.tcp://192.168.1.20:4840/milo. host and port are required (the driver's validate() checks both are non-empty); path may keep the default /. During endpoint discovery the driver connects to the first endpoint the server returns.

Point attributes (point-attribute)

Fill in these two on each collected point; together they form the target node's NodeId.

AttributecodeTypeDefaultDescription
NamespacenamespaceINT5Namespace index
TagtagSTRINGTAGString identifier (node name)

NodeId = namespace + tag

The driver combines namespace (the namespace index) and tag (the string identifier) into NodeId(namespace, tag) for reads and writes. For example, namespace=2 and tag=Demo.Static.Float resolve to the node named Demo.Static.Float under namespace 2. The Point's data type (the pointTypeFlag of the Point) must match the node's actual value type — read values are stringified before reporting, while writes pick the OPC UA data type from the Point type.

Write commands have no separate attribute

The OPC UA driver has no command-attribute. To write a value to a node it reuses the Point's own namespace and tag to locate the target node, and the value type is decided by the Point type — the driver supports writing INT / LONG / FLOAT / DOUBLE / BOOLEAN / STRING (see writeNode() in the source). So once a writable Point has its namespace and tag set, you can issue write commands without filling in any command attribute.

Collection and health check

These come from dc3.driver.schedule and dc3.driver.health in application.yml; they are driver-level defaults, not configured per device.

ItemConfig keyDefaultDescription
Collection cycleschedule.read.cron0/30 * * * * ?Read all points once every 30 seconds
Health checkhealth.device.cron0/15 * * * * ?Probe once every 15 seconds
Lease timeouthealth.device.timeout45 (seconds)Mark offline if not renewed in time

The health check runs an idempotent connect() probe with the device's client: if it connects, the device is online; otherwise offline.

Troubleshooting

The default port is 18600, not the standard 4840

The port default in the yml is 18600 (the port of the local built-in Milo sample server). In production, the vast majority of OPC UA servers use the standard port 4840, so when onboarding a real device you must set port to the port the server actually listens on — do not just keep the default. path must also match the server's endpoint path: some servers expose the root path (set /), others a sub-path (such as /milo or /OPCUA/SimulationServer). Getting it wrong means the connection fails.

  • Anonymous identity rejected: the driver connects with an anonymous identity (AnonymousProvider). If the server enforces username/password and disallows anonymous access, the connection is rejected. Enable anonymous access on the server, or open an anonymous policy for that endpoint first.

  • Device stays offline: the health check runs a connect() probe every 15 seconds and marks the device offline after repeated failures. First confirm the endpoint address formed from host/port/path is correct and reachable (telnet host port or nc -vz host port to verify the port is open), then confirm the server process is running and the firewall does not block the opc.tcp port.

  • Read value is null or status code is not Good: when reading a node, if the StatusCode is not Good or the value is empty, the driver throws ReadPointException and proactively disconnects and evicts that connection ( reconnecting on the next cycle). Common causes: a wrong NodeId (namespace or tag does not exist), no read permission on the node, or the node currently has no value. Use a tool such as UaExpert to verify the node ns=<namespace>;s=<tag> actually exists and is readable.

  • Read/write timeout: the driver's connect timeout is 5 s, read timeout 1 s, write timeout 1 s. Network jitter or a slow server easily causes timeouts, which likewise evict the connection and trigger a reconnect. If the server is genuinely slow, investigate the link latency on the network side rather than raising the per-point timeout.

  • Write command has no effect: the write value type must be one of INT / LONG / FLOAT / DOUBLE / BOOLEAN / STRING, and must be compatible with the actual data type of the server node; on a type mismatch the server returns a non-Good status and the write is treated as failed. Confirm the Point's pointTypeFlag matches the server node type and that the node is writable by the client.

  • Certificate-related errors: on startup the driver generates a self-signed certificate dc3-opc-ua-client.pfx ( PKCS12, default password password, overridable via the OPCUA_KEYSTORE_PASSWORD environment variable) under the working directory dc3/opc-ua. If that directory is not writable, or certificate generation fails, the driver falls back to a plain anonymous connection (no client certificate). When the server's security policy requires a client certificate, a plain anonymous connection fails the handshake — make sure the certificate directory is writable and the generated client certificate is "trusted" on the server.

How it lands in IoT DC3

  • dc3.driver.code: OpcUaDriver — the driver's stable routing identifier in the system. Data and command paths address by it, so do not change it casually.
  • Read: ✓ implemented. On each collection cycle it calls readValue() per point to read the node, stringifies the value, and reports it as a PointValue.
  • Write: ✓ implemented. On a write command it reuses the Point's namespace/tag to locate the node and writes INT/LONG/FLOAT/DOUBLE/BOOLEAN/STRING based on the Point type.
  • Subscribe/report: — not provided. This driver is a master-polling model; it does not subscribe to the OPC UA server's data-change notifications (Subscription/MonitoredItem), only reads on a cycle.

This matches the driver capability matrix (read ✓ / write ✓ / subscribe —).

Implementation status: available

OpcUaDriverCustomServiceImpl's read() / write() / health() / validate() / event() are all complete implementations (built on Eclipse Milo), not a skeleton. Reading nodes, writing the six types, connection caching and reconnect-on-failure, self-signed certificate generation, and clearing connections on device update/delete are all in place — it can be pointed at a real OPC UA server directly.

Minimal onboarding example

Onboard a float node on the endpoint opc.tcp://192.168.1.20:4840/milo:

  1. Create a Device using OPC UA Driver, and set the driver attributes host=192.168.1.20, port=4840, path=/milo.
  2. Add a temperature Point (pointTypeFlag=FLOAT, READ_ONLY) to the Profile bound to the device, and set the point attributes namespace=2, tag=Demo.Static.Float.
  3. Start the driver, and within 30 seconds you will see the collected value in PointValue.

See Device onboarding for the full walkthrough.