OPC UA Driver

dc3-driver-opc-ua connects OPC UA servers to IoT DC3 — it targets nodes on an OPC UA server, periodically reads node values, and supports writing values to nodes.

OPC UA (OPC Unified Architecture) is the cross-platform data-interoperability standard for industrial automation. PLCs, SCADA, MES, and edge gateways commonly embed an OPC UA server that exposes field data as a "node tree." Each node is uniquely identified by a NodeId, which combines a "namespace index" and an "identifier." This driver acts as the OPC UA client, using Eclipse Milo to connect over the opc.tcp:// binary protocol to one or more servers, then reading and writing node values according to the namespace and identifier configured on each Point.

  • Driver name / code: OPC UA Driver / OpcUaDriver
  • Type: DRIVER_CLIENT (actively connects to the server)

Driver configuration (device-level driver-attribute)

When onboarding an OPC UA server device, fill in these attributes on the Device:

AttributecodeTypeDefaultDescription
HosthostSTRINGlocalhostOPC UA host
PortportINT18600OPC UA port
PathpathSTRING/OPC UA endpoint path

The three combine into the endpoint address opc.tcp://<host>:<port><path>, e.g. opc.tcp://192.168.1.20:4840/milo.

Point configuration (point-attribute)

Fill in these on each collected Point; together they locate one OPC UA node (NodeId):

AttributecodeTypeDefaultDescription
NamespacenamespaceINT5OPC UA namespace index
TagtagSTRINGTAGOPC UA node tag name

NodeId = namespace + tag

The driver combines namespace (the namespace index) and tag (the string identifier) into a NodeId for reads and writes. For example, namespace=2 and tag=Demo.Static.Float resolve to the node named Demo.Static.Float under namespace 2. The Point's data type (the pointTypeFlag of the Point) must match the node's actual value type.

Write command configuration

The OPC UA driver has no separate command-attribute. To write a value to a node, it reuses the Point's own namespace and tag to locate the target node, and the value type is decided by the Point type — the driver supports writing INT / LONG / FLOAT / DOUBLE / BOOLEAN / STRING. So once a writable Point has its namespace and tag set, you can issue write commands without filling in any command attribute.

Collection and health

  • Collection cycle: default cron 0/30 * * * * ? (one read round every 30 seconds).
  • Health/online: device health check defaults to cron 0/15 * * * * ?, with a lease timeout of 45 seconds (the health check makes a connect probe to the server) — see Device for the online-status mechanism.

Minimal onboarding example

Onboard a float node on the endpoint opc.tcp://192.168.1.20:4840/milo:

  1. Create a Device using OPC UA Driver, and set the driver attributes host=192.168.1.20, port=4840, path=/milo.
  2. Add a temperature Point (pointTypeFlag=FLOAT, READ_ONLY) to the Profile bound to the device, and set the point attributes namespace=2, tag=Demo.Static.Float.
  3. Start the driver, and within 30 seconds you will see the collected value in PointValue.

Common pitfalls

The default port is 18600, not the standard 4840

The port default in the yml is 18600 (the port of the local built-in Milo sample server). In production, the vast majority of OPC UA servers use the standard port 4840, so when onboarding a real device you must set port to the port the server actually listens on — do not just keep the default.

path must also match the server's endpoint path: some servers expose the root path (set /), others a sub-path (such as /milo or /OPCUA/SimulationServer). Getting it wrong means the connection fails.

Anonymous identity, certificate auto-generated

The driver connects with an anonymous identity (AnonymousProvider). On startup, if no client certificate exists under the working directory dc3/opc-ua, the driver auto-generates a self-signed certificate (dc3-opc-ua-client.pfx) to use for the connection — no manual placement required. If the server enforces username/password auth and disallows anonymous, the anonymous connection is rejected — enable anonymous on the server first.