Serial Driver

dc3-driver-serial connects RS232/RS485/RS422 serial devices to IoT DC3 — it periodically sends the HEX command configured on each Point, reads back the raw bytes, parses them into a value by frame header/footer, checksum, data offset and format, and supports commands that write values to the device.

Serial is the plainest yet most universal way to wire up the industrial floor: RS232 point-to-point, RS485/RS422 buses are widely used by meters, transmitters, barcode scanners, PLC serial modules, and more. Many devices do not speak a standard protocol but a proprietary "send some bytes, get some bytes back" frame. This driver acts as the serial master: it opens a serial port via jSerialComm, caches one connection per device, sends the HEX command you configured for each point, then slices the data region out of the response by its frame structure and decodes it in the format you specify (HEX/ASCII/BINARY/FLOAT).

  • Driver name / code: Serial Port Driver / SerialDriver
  • Type: DRIVER_CLIENT (actively opens the port and polls the device)

Two terms first

HEX command: a byte string written in hexadecimal, e.g. 01 03 00 00 00 0A C5 CD; the spaces are only for readability and map to the actual bytes sent. Frame: the full chunk of bytes the device replies with, usually made up of a header, a data region, an optional checksum, and a footer; this driver uses the header/footer plus offset/length to "cut" the real data region out of the response.

Driver configuration (device-level driver-attribute)

When onboarding a serial device, fill in these attributes on the Device; they decide how the serial port is opened (line parameters):

AttributecodeTypeDefaultDescription
Serial PortportSTRING/dev/ttyUSB0Serial port device path
Baud RatebaudRateINT9600Baud rate (1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200)
Data BitsdataBitsINT8Data bits (5, 6, 7, 8)
Stop BitsstopBitsINT1Stop bits (1, 2)
ParityparityINT0Parity (0=None, 1=Odd, 2=Even)
TimeouttimeoutINT1000Read timeout in milliseconds

Point configuration (point-attribute)

On each collected Point, set what to send, how to slice the response, and what format to decode in.

AttributecodeTypeDefaultDescription
Send CommandsendCommandSTRING(empty)HEX command to send (e.g. 01 03 00 00 00 0A C5 CD)
Receive LengthreceiveLengthINT0Expected response length in bytes (0=auto detect)
Frame HeaderframeHeaderSTRING(empty)Frame header in HEX (e.g. 01 03)
Frame FooterframeFooterSTRING(empty)Frame footer in HEX (e.g. 0D 0A)
Data OffsetdataOffsetINT0Data region offset from frame start
Data LengthdataLengthINT0Data region length in bytes (0=until frame footer)
Checksum TypechecksumTypeSTRINGNONEChecksum type: NONE, CRC16, XOR
Data FormatdataFormatSTRINGHEXData format: HEX, ASCII, BINARY, FLOAT
Byte OrderbyteOrderSTRINGBIGByte order: BIG, LITTLE

Parsing order: slice the frame first, then decode

After receiving a response, the driver first locates the frame using frameHeader/frameFooter, slices the data region by dataOffset/dataLength and verifies it by checksumType, then decodes it into a point value by dataFormat + byteOrder. The Point's data type (the pointTypeFlag of the Point) should match dataFormat: 2/4/8-byte quantities are assembled into integers or floats according to byteOrder, and FLOAT uses 4 bytes (single precision) or 8 bytes (double precision).

Write command configuration (command-attribute)

A writable Point sets these on the write command:

AttributecodeTypeDefaultDescription
Send CommandsendCommandSTRING${value}HEX command template with the ${value} placeholder
Byte OrderbyteOrderSTRINGBIGByte order for encoding the written value: BIG, LITTLE

On write, the driver renders the command param into the ${value} slot of the sendCommand template, converts it to bytes, and sends the whole frame.

Collection and health

  • Collection cycle: default cron 0/30 * * * * ? (one polling round every 30 seconds).
  • Health/online: device health check defaults to cron 0/15 * * * * ?, with a lease timeout of 45 seconds; the driver treats a device as online based on whether its serial port is open — see Device for the online-status mechanism.

Minimal onboarding example

Onboard a Modbus RTU-style temperature transmitter on /dev/ttyUSB0 at 9600-8-N-1 (slave 1, reads a holding register, responds with 01 03 02 <2 data bytes> <2 CRC bytes>):

  1. Create a Device using Serial Port Driver, and set the driver attributes port=/dev/ttyUSB0, baudRate=9600, dataBits=8, stopBits=1, parity=0.
  2. Add a temperature Point (READ_ONLY) to the Profile bound to the device, and set the point attributes sendCommand=01 03 00 00 00 01 84 0A, frameHeader=01 03, dataOffset=3, dataLength=2, dataFormat=BINARY, byteOrder=BIG.
  3. Start the driver, and within 30 seconds you will see the collected value in PointValue.

Common pitfalls

You must compute the CRC in sendCommand yourself

This driver does not append a Modbus CRC for you — sendCommand is sent verbatim as a single byte string, so the checksum bytes must be computed and written in by you (the 84 0A above is exactly that CRC). A wrong CRC means the device either does not reply or returns an exception frame. checksumType only verifies the response and never rewrites the command you send.

dataOffset counts from frame start — don't treat the header as data

dataOffset/dataLength are byte offsets relative to the start of the whole frame, not relative to the data region. In the Modbus RTU response 01 03 02 ..., the payload starts at the 4th byte, so dataOffset=3 and dataLength=2. Forgetting the header makes you decode the address/function code as data.

One driver instance can serve multiple serial devices

A single driver process caches an independent serial connection per device and can serve several devices on different port paths at once. But multiple devices on the same physical port (an RS485 bus) each need their own Device, distinguished by their own sendCommand (with different station addresses); the driver polls them point by point.